Model No.︰TAN-30
Brand Name︰linsam
Country of Origin︰China
Unit Price︰CNY ¥ 50000 / pc
Minimum Order︰5 pc
Model | TAN-10 | TAN-12 | TAN-15 | TAN-20 | TAN-25 | TAN-30 | TAN-50 | ||
Rated heating capacity | kW | 38.0 | 47.0 | 58.0 | 76.0 | 92.0 | 103.0 | 182.0 | |
Rated power input | kW | 8.2 | 10.2 | 12.7 | 16.7 | 20.5 | 23.2 | 41 | |
Hot water output | T/H | 0.77 | 0.97 | 1.21 | 1.55 | 1.93 | 2.2 | 3.87 | |
Input current | A | 13.34 | 16 | 20 | 26.51 | 33.1 | 40 | 66 | |
Max running current | A | 24 | 28 | 36 | 48 | 56 | 72 | 112 | |
COP | kW/kW | 4.6 | 4.6 | 4.6 | 4.55 | 4.5 | 4.44 | 4.44 | |
Rated/Max outgoing water temp | ℃ | 55℃/60℃ | |||||||
Power supply | V/Ph/Hz | 380V/3N/50Hz | |||||||
Noise level | dB(A) | 63 | 64 | 66 | 68 | 68 | 68 | 72 | |
Unit dimension | Length(A) | mm | *1500/1450 | 1500 | 1500 | 1850 | 2000 | 2000 | 2300 |
Width(B) | mm | *440/780 | 700 | 800 | 1000 | 1100 | 1100 | 1260 | |
Height(C) | mm | *1705/1050 | 1350 | 1500 | 1950 | 1930 | 2070 | 2250 | |
Unit Weight | kg | 245 | 280 | 310 | 560 | 630 | 850 | 1350 | |
Operating temp limits: Air | ℃ | -15℃-43℃ | |||||||
Throttle | Electronic expansion valve / Thermal expansion valve optional | ||||||||
Refrigerant type | R410A/R417A/R407C optional | ||||||||
Refrigerant charge qty | kg | 2.0*2 | 2.3*2 | 2.8*2 | 5.5*2 | 6.0*2 | 6.5*2 | 6.0*4 | |
Compressor | Hermetically sealed scroll compresor ( Copeland, Sanyo, Daikin optional ) | ||||||||
Compressor qty | pcs | 2 | 2 | 2 | 2 | 2 | 2 | 4 | |
Evaporator | High efficiency blue finned aluminium tube heat exchanger | ||||||||
Controller | LCD controller easy operation(built-in high pressure, low pressure, over heating, over current, water flow, phase protections and so on) | ||||||||
Hot water side | Heat exchanger type | High efficiency tank type/ high efficiency tube in tube heat exchanger optional | High efficiency tank type / Shell tube heat exchanger | ||||||
Water flow | m3/h | 6.50 | 7.80 | 9.80 | 13.00 | 16.50 | 20.50 | 32.00 | |
Conncetion in / out | DN | 32 | 32 | 40 | 50 | 50 | 65 | 80 | |
Test conditions:air source side DB/WB is 20℃/15℃, inlet water temp 15℃, outlet water temp 55℃. |
Payment Terms︰ TT/LC